TH230D40NZ-6
Keywords:
- Description
- Parameters
- Application
- Product Info
-
Rectifier / Charging module
3 phase input: 380VAC
Output: 190-300VDC
Fan cooling
-

TH230D40NZ-6 Input voltage 3 phase 380VAC(-15%~+20%) Input frequency 45~55Hz Range of output voltage 176~300VDC Current-limit setting range 4~42A Efficiency Peak efficiency≥93% Power factor Full load≥0.98 Harmonic current Half load ≤8%,full load ≤5% Stabilized voltage precision ≤±0.5% Stabilized current precision ≤±1% Peak-ripple factor ≤1% Noise Rated noise ≤60dB Current sharing imbalance for modules in parallel ≤±3% Soft start time 3~8S Storage temperature -25~+60℃ Woking temperature -10~+40℃ Heat dissipation mode of module Compulsory fan cooling Automatic current limiting characteristics When the output current exceeds the output current limit setting value, the output current will be constant and the output current will not increase. Over output voltage protection With hardware and software dual overvoltage protection Output short circuit protection characteristics When the output is short-circuited, the module will automatically rewind to prevent damage, and will automatically resume operation after the fault is eliminated. Dielectric strength Input to shell 2100VAC 1 minute
leakage current ≤10mA no breakdown, no electric arcing.Output to shell 2100VAC 1 minute leakage current ≤10mA no breakdown, no electric arcing. Input to output 2100VAC 1 minute leakage current ≤10mA
no breakdown, no electric arcing.Insulation resistance ≥10MΩ(1000V insulation meter test) The EMC characteristics of module TH230D40NZ-6 are as below.
(1) Immunity of interference
ESD: GB/T 17626.2, level 4.
RS (Radiated susceptibility): GB/T 17626.3, level 3.
ETF (Electrical fast transient): GB/T 17626.4, level 4.
Surge: GB/T 17626.5, level 3.
CS (Conducted susceptibility): GB/T 17626.6, level 3.
PMS (Power-frequency magnetic susceptibility): GB/T 17626.8, level 4.
Damped oscillatory magnetic field immunity: GB/T 17626.10, level 4.
Oscillatory wave immunity: GB/T 17626.12, level 3.(2) Electromagnetic emission limit
The conducted emission limits are shown in the table belowFrequency range/MHz Emission limit /dB(μV) Quasi-peak value Mean value 0.15~0.5 (does not include 0.5) 79 66 0.5~30 73 60 Radiated emission limits are shown in the table below.
Frequency range/MHz RE limits at 10m measurement distance /dB(μV/m) Quasi-peak value 30~230 40 230~1 000 (does not include 230) 47 -
For Power System:
DC Operating Power Supply: Provides highly reliable DC power for relay protection, automatic devices, circuit breaker opening and closing, etc. in power plants and substations, and is the key to safe operation of power stations.