THD500B48-S
Keywords:
THD500B48-S
subclassification:
Model:
cp1602
Product description
Technical parameters:
Weight :1kg
★ Size :168mm×110mm×50mm(width × height × depth, without panel connector)
Cooling method: natural cooling
★ Operating temperature :-40℃ ~ 70℃
Ac input voltage VAC:220±20%
Dc output voltage VDC:53.5±0.5
★ DC output current A:2
★ Battery charging voltage V: 53.5
★ Battery charging current A: 0.5
★ Efficiency: ≥ 84%
★ Ripple: ≤ 400mV
Main features of the module:
Small size, high conversion efficiency, stable performance, primary side isolation, high isolation intensity; Metal reinforced packaging, dustproof, moisture-proof, strong anti-interference ability; Wide input range, strong adaptability of power grid; Meet the output capacity of 12A load greater than 15S; Good electromagnetic compatibility, all technical indicators meet DL/T 721-2013 standard requirements. Plug and pull type terminal, easy to install, debug and use.
System performance characteristics:
This product is especially suitable for opening and closing station, ring network terminal equipment (DTU) system, supporting 7 ~ 40AH lead-acid battery or colloid maintention-free battery, form a complete set of power supply system with backup battery, can effectively meet the control unit, communication unit, switch unit power demand, and ensure that in the case of external power failure, Provide uninterrupted power to the load.
Welcome to your message for consultation