Product Center
Product Center
Contact Info
Service Hotline:
Company email:
Headquarters address:
No. 350, Lijiang Road, Shijiazhuang High-tech Zone
JYJC-32G
Keywords:
- Description
- Parameters
- Application
- Product Info
-
Product Introduction
The JYJC-32G module developed by Shijiazhuang Tonghe Electronics Technology Co., Ltd. monitors busbar insulation and branch circuit insulation, and transmits the data to the monitoring host via an RS485 interface.
Product Features
• Can measure the ground voltage and ground resistance of a single busbar segment.
• Busbar support for early warning and alarm configuration
• When there is no insulation fault, the busbar-to-ground voltage fluctuation is less than Ukm/10 (where Ukm is the busbar voltage).
• Can detect ground resistance when both the positive and negative busbars are present simultaneously.
• The measurable range for busbar resistance is 10 to 99.9 kΩ.
• Can detect insulation on 32 circuits
• Branch circuits support early warning and alarm configuration.
• Can detect ground resistance when both the positive and negative branches are present simultaneously.
• Busbar insulation can detect AC voltage intrusion.
• Maximum inspection time per unit ≤ 40 s
• Supports four operating modes: active, passive, master, and slave.
• Supports the RS485 communication interface, facilitating communication with power monitoring devices. -
Technical indicators
Mailing address range
0x2F~0x3E (the first one starts at address 0x2F)
Bus voltage range
190~286VDC
Busbar Resistance Measurement Range
10~99.9KΩ
Ground voltage fluctuation range
<=|U kilometer /10|, (U kilometer For busbar voltage)
Measurement range of branch resistance values
10~99.9KΩ
AC voltage measurement range
10~242VAC
Sensor power supply
±12.0V
Power supply
Power input, range 88–286 VDC
Size
116*202*45mm (front view: height*width*depth)
Interface Definition
Branch Detection
1–32, output of leakage current sensors for branches 1–32
GND, +, -
Sensor power supply (+12V, -12V, ground)
K1
Insulation fault relay output, normally open contact. Rating: 250 VAC/1 A, 30 VDC/0.5 A, 220 VDC/0.1 A. It is recommended that the node capacity not exceed 220 VDC/50 mA.
KM1
Control the positive voltage of the mother board.
HM1
Positive bus voltage
-M1
Bus negative
COM
Master–slave interface when operating in master–slave mode
Address
Device address DIP switch
RS485
RS485 communication interface
Power Supply
Power connector