DCXJ-18
+
  • DCXJ-18

DCXJ-18

The DCXJ-18 module developed by Shijiazhuang Tonghe Electronics Technology Co., Ltd. can acquire the voltage and ambient temperature data of 18 12V battery cells and transmit this information to a monitoring system via RS‑485 communication.


Keywords:


Share now

  • Description
  • Parameters
  • Application
  • Product Info
  • Product Introduction

    The DCXJ-18 module, developed by Shijiazhuang Tonghe Electronics Technology Co., Ltd., can acquire the voltage and ambient temperature data of 18 12V battery cells and transmit this information to a monitoring system via RS‑485 communication.

    Product Features

    • Measure and detect the voltage of 18 12V battery cells.
    • Acquire one channel of ambient temperature
    • Supports RS485 communication

  • Technical indicators

    Single-cell voltage

    Maximum of 18 channels can be acquired, with a voltage measurement range of 1–17 V.

    Ambient temperature

    Channel 1: Built-in acquisition without configuring a temperature-sensing probe.

    Dial code

    DIP switch 1# (0: battery sampling with 2 decimal places; 1: battery precision with 3 decimal places)
    DIP switch #2, DIP switch #3, DIP switch #4: Address code
    (Setting the DIP switch to the ON position corresponds to 0.)

    Work indicator light

    Green, steadily lit when the power supply is normal.

    RS485 interface

    RS485 interface

    Power supply

    Power input, range 88–286 VDC

    Size

    125*152*45mm (front view: height*width*depth)

    Interface Definition

    Digital Input SI 1

    1# Digital input signal, connected to the open/close status of one incoming line switch.

    Digital Input SI 2

    2# Digital input signal, connected to the trip status of one incoming line switch.

    Digital Input SI 3

    3# Digital input signal, connected to the open/close status of two incoming line switches.

    Digital Input SI 4

    4# Digital input signal, connected to the trip status of two incoming line switches.

    Digital Input SI 5

    5# Digital input signal, dual-power supply switching status of channel 1

    Digital Input SI 6

    6# Digital input signal, dual-power supply switching status of two circuits

    Digital Input SI 7

    7# Digital Signal Input

    Digital Input SI 8

    8# Digital Signal Input

    Digital Input SI 9

    9# Digital Signal Input

    Digital Input SI 10

    10# Digital Signal Input

    Digital Input SI 11

    11# Digital Signal Input

    Digital Input SI 12

    12# Digital Signal Input

    Digital Input SI 13

    13# Digital Signal Input

    Digital Input SI 14

    14# Digital Signal Input

    Digital Input SI 15

    15# Digital Signal Input

    Digital Input SI 16

    16# Digital Signal Input

    COM

    Common terminal for discrete input signals

    K1

    Control of Switching Circuit 1

    K2

    Control two-way switching

    K3

    Control of Channel 0: Both power supplies are disconnected (Note: Customized configuration)

    K4-K10

    Relay Output (Spare)

    SYS

    Monitoring failure

    AC Channel 0 Voltage VAC0

    Three-phase AC voltage measurement interface, capable of controlling AC automatic transfer.

    AC Circuit 1 Voltage VAC1

    Three-phase AC voltage measurement interface, capable of controlling AC automatic transfer.

    AC voltage, 2 channels, VAC2

    Three-phase AC voltage measurement interface, capable of controlling AC automatic transfer.

    AC busbar current ACI

    Three-phase AC current measurement interface

    1# AC busbar current ACI

    Three-phase AC current measurement interface

    2# AC Bus Current ACI

    Three-phase AC current measurement interface

    RS485 interface

    RS485 communication interface, providing two ports for convenient wiring.

    Power Supply

    Power supply

Get a free product quote

Please provide your phone number and email address, and we’ll get in touch with you promptly within one business day to resolve your issue as soon as possible.

Related products

The H series is manufactured using thick-film hybrid integration technology. Its enclosure features a fully sealed metal structure, and the interior is filled with inert gas.
Learn more Learn more
This series of fire‑fighting power supplies is a core power‑supply device independently developed by our company, specifically designed to ensure reliable electrical power during emergencies such as fires. It truly serves as a guardian of the “lifeline.”